Design for installation in separating concrete and masonry walls and ceilings and lightweight plasterboard walls of fire compartments with fire resistance class EIS 120
Readiness for installation with all wall options as delivered no additional frames needed
Manufacture in accordance with the ISO 9001 quality system
VTT, the Technical Research Centre of Finland, is responsible for external quality control
Installation in circular ducts with diameter 160 to 500 mm
Double sealing, ensuring that the blades are tight when the fire damper is closed before and during a fire
Fire damper casing complying with the tightness requirements for Class C, EN 1751
Fire damper tightness meeting smoke damper requirement S of standard EN 1366-2
Suitability for use in ducts with a maximum pressure of 3100 Pa
Damper closing tests performed at 15 m/s duct velocity
Product Models and Accessories
Models equipped with either manual or electric actuators